Model
|
Number of channels
|
Available sensor
|
Input specifications
|
Compatible CPU module
|
Item
|
Temperature input
|
FX5U
|
FX5UC
|
FX5UJ
|
FX5S
|
|
FX5-4AD-PT-ADP
|
4 ch
|
Usable resistance temperature detector Pt100 Ni100
|
Input range
|
[Typical example] Pt100: -200 to +850˚C Ni100: -60 to +250˚C
|
○ Max. 4 modules
|
○ Max. 4 modules
|
○ Max. 2 modules
|
○ Max. 4 modules
|
Resolution
|
0.1˚C
|
|
FX5-4AD-TC-ADP
|
4 ch
|
Thermocouple K, J, T, B, R, S
|
Input range
|
[Typical example] K type: -200.0 to 1200˚C J type: -40.0 to 750˚C
|
○ Max. 4 modules
|
○ Max. 4 modules
|
○ Max. 2 modules
|
○ Max. 4 modules
|
Resolution
|
0.1 to 0.3˚C (depending on the sensor used)
|
|
FX5-8AD
|
8 ch
|
Usable resistance temperature detector Pt100 Ni100
|
Input range
|
[Typical example] Pt100: -200 to +850˚C Ni100: -60 to +250˚C
|
○
|
*1 ○
|
○
|
×
|
Resolution
|
0.1˚C
|
Thermocouple K, J, T, B, R, S
|
Input range
|
[Typical example] K type: -270.0 to 1200˚C J type: -40.0 to 750˚C
|
Resolution
|
0.1 to 0.3˚C (depending on the sensor used)
|
|
FX5-4LC
|
4 ch
|
Platinum resistance thermometer sensor Pt100, JPt100, Pt1000
|
Input range
|
[Typical example] 3-wire Pt100: -200 to 600˚C 3-wire JPt100: -200 to 500˚C 2-wire/3-wire Pt1000: -200.0 to 650.0˚C
|
○
|
*1 ○
|
○
|
×
|
Resolution
|
0.1˚C or 1˚C (depending on the sensor used)
|
Thermocouple K, J, R, S, E, T, B, N JIS C 1602-1995, PLⅡ, W5Re/W26Re, U, L
|
Input range
|
[Typical example] K type: -200.0 to 1300˚C J type: -200.0 to 1200˚C
|
Resolution
|
0.1˚C or 1˚C (depending on the sensor used)
|
Micro voltage input
|
Input range
|
0 to 10 mV DC 0 to 100 mV DC
|
Resolution
|
0.5 μV or 5.0 μV (depending on the sensor used)
|
|
FX3U-4LC
|
4 ch
|
Platinum resistance thermometer sensor Pt100, JPt100, Pt1000
|
Input range
|
[Typical example] 3-wire Pt100: -200 to 600˚C 2-wire/3-wire Pt1000: -200.0 to 650.0˚C
|
*2 ○ Max. 6 to 8 modules *3
|
*2 ○ Max. 6 modules
|
×
|
×
|
Resolution
|
0.1˚C or 1˚C (depending on the sensor used)
|
Thermocouple K/J/R/S/E/T/B/ N/PLII/W5Re/ W26Re/U/L type
|
Input range
|
[Typical example] K type: -200.0 to 1300˚C J type: -200.0 to 1200˚C
|
Resolution
|
0.1˚C or 1˚C (depending on the sensor used)
|
Low voltage input
|
Input range
|
0 to 10 mV DC 0 to 100 mV DC
|
Resolution
|
0.5 μV or 5.0 μV (depending on the sensor used)
|