Modular 3-phase control relay, 8 A, 2 CO, 380...480 V AC
| Range of product | Harmony Control Relays |
|---|---|
| Relay type | Control relay |
| Product or component type | 3-phase control relay |
| Network number of phases | 3 phases |
| Relay name | RM22TR |
| Relay monitored parameters | Overvoltage and undervoltage detection Phase sequence Phase failure detection |
| Time delay type | Adjustable 0.1...30 s, +/- 10 % of the full scale value Tt- time delay upon fault |
| Switching capacity in VA | 2000 VA |
| Measurement range | 380...480 V voltage AC |
| Contacts type and composition | 2 C/O |
| Reset time | 1500 ms at maximum voltage |
|---|---|
| Maximum switching voltage | 250 V AC |
| Minimum switching current | 10 mA at 5 V DC |
| Maximum switching current | 8 A AC |
| [Us] rated supply voltage | AC/DC |
| Supply voltage limits | 304…576 V AC |
| operating limits | - 20 % + 20 % Un |
| Power consumption in VA | 15 VA at 480 V AC 60 Hz |
| Voltage detection threshold | < 100 V AC |
| supply voltage frequency | 50...60 Hz +/- 10 % |
| Output contacts | 2 C/O |
| nominal output current | 8 A |
| Setting accuracy of the switching threshold | +/- 10 % of the full scale |
| Switching threshold drift | <= 0.05 % per degree centigrade depending permissible ambient air temperature <= 1 % within the supply voltage range |
| Setting accuracy of time delay | 10 P |
| Time delay drift | <= 0.05 % per degree centigrade depending permissible ambient air temperature <= 1 % within the supply voltage range |
| Hysteresis | 2 % fixed of selectable |
| Run-up delay at power-up | 650 ms |
| Maximum measuring cycle | 150 ms measurement cycle as true rms value |
| Threshold adjustment voltage | 2...20 % of Un selected |
| Voltage range | 380...480 V phase to phase |
| Repeat accuracy | +/- 0.5 % for input and measurement circuit +/- 3 % for time delay |
| Measurement error | < 1 % over the whole range with voltage variation < 0.05 %/°C with temperature variation |
| Response time | <= 300 ms |
| Overvoltage category | III conforming to IEC 60664-1 III conforming to UL 508 |
| Insulation resistance | > 100 MOhm at 500 V DC conforming to IEC 60255-27 |
| Mounting position | Any position |
| Connections - terminals | Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Self-extinguishing plastic |
| Status LED | LED (yellow) relay ON LED (green) power ON |
| Mounting support | 35 mm DIN rail conforming to IEC 60715 |
| Electrical durability | 100000 cycles |
| Mechanical durability | 10000000 cycles |
| Utilisation category | AC-15 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 AC-1 conforming to IEC 60947-4-1 DC-1 conforming to IEC 60947-4-1 |
| [Un] rated nominal voltage | , self-powered |
| Safety reliability data | MTTFd = 388.1 years B10d = 350000 |
| Contacts material | Cadmium free |
| Control type | With test button |
| Width | 22.5 mm |
| Net weight | 0.09 kg |