Product | |
Article Number (Market Facing Number) | 6ES7231-4HF32-0XB0 |
Product Description | SIMATIC S7-1200, Analog input, SM 1231, 8 AI, +/-10 V, +/-5 V, +/-2.5 V, or 0-20 mA/4-20 mA, 12 bit+sign or (13 bit ADC) |
Product family | SM 1231 analog input modules |
General information
|
|
Product type designation
|
SM 1231, AI 8x13 bit
|
Supply voltage
|
|
Rated value (DC)
|
24 V
|
Input current
|
|
Current consumption, typ.
|
45 mA
90 mA
|
from backplane bus 5 V DC, typ.
|
|
Power loss
|
|
Power loss, typ.
|
1.5 W
|
Analog inputs
|
|
Number of analog inputs
|
8; Current or voltage differential inputs
|
permissible input voltage for voltage input (destruction
|
35 V
|
limit), max.
|
|
permissible input current for current input (destruction
|
40 mA
|
limit), max.
|
|
Cycle time (all channels) max.
|
625 µs
|
Input ranges
|
|
● Voltage
|
Yes; ±10V, ±5V, ±2.5V
|
● Current
|
Yes; 4 to 20 mA, 0 to 20 mA
|
● Thermocouple
|
No
|
● Resistance thermometer
|
No
|
● Resistance
|
Yes
|
Input ranges (rated values), voltages
|
|
● -10 V to +10 V
|
Yes
|
— Input resistance (-10 V to +10 V)
|
≥9 MOhm
|
● -2.5 V to +2.5 V
|
Yes
|
— Input resistance (-2.5 V to +2.5 V)
|
≥9 MOhm
|
● -5 V to +5 V
|
Yes
|
— Input resistance (-5 V to +5 V)
|
≥9 MOhm
|
Input ranges (rated values), currents
|
|
● 0 to 20 mA
|
Yes
|
— Input resistance (0 to 20 mA)
|
280 Ω
|
● 4 mA to 20 mA
|
Yes
|
— Input resistance (4 mA to 20 mA)
|
280 Ω
|
Thermocouple (TC)
|
|
Temperature compensation
|
|
— parameterizable
|
No
|
Analog value generation for the inputs
|
Integration and conversion time/resolution per channel
|
|
● Resolution with overrange (bit including sign), max.
● Integration time, parameterizable
● Interference voltage suppression for interference frequency f1 in Hz
|
12 bit; + sign Yes
40 dB, DC to 60 V for interference frequency 50 / 60 Hz
|
Smoothing of measured values
|
|
● parameterizable
● Step: None
● Step: low
● Step: Medium
● Step: High
|
Yes Yes Yes Yes
Yes
|
Errors/accuracies
|
|
Temperature error (relative to input range), (+/-)
|
25 °C ±0.1%, to 55 °C ±0.2% total measurement range
|
Basic error limit (operational limit at 25 °C)
|
|
● Voltage, relative to input range, (+/-)
● Current, relative to input range, (+/-)
|
0.1 %
0.1 %
|
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
|
|
● Common mode voltage, max.
|
12 V
|
Interrupts/diagnostics/status information
|
|
Alarms
|
Yes
Yes
|
Diagnostics function
|
|
Alarms
|
|
● Diagnostic alarm
|
Yes
|
Diagnoses
|
|
● Monitoring the supply voltage
● Wire-break
|
Yes
Yes
|
Diagnostics indication LED
|
|
● for status of the inputs
● for maintenance
|
Yes
Yes
|
Standards, approvals, certificates
|
|
CE mark
|
Yes Yes Yes Yes Yes Yes Yes
Yes
|
CSA approval
|
|
UL approval
|
|
cULus
|
|
FM approval
|
|
RCM (formerly C-TICK)
|
|
KC approval
|
|
Marine approval
|
|
Ambient conditions
|
|
Free fall
|
|
● Fall height, max.
|
0.3 m; five times, in product package
|
Ambient temperature during operation
|
|
● min.
● max.
● horizontal installation, min.
● horizontal installation, max.
● vertical installation, min.
● vertical installation, max.
|
-20 °C
60 °C
-20 °C
60 °C
-20 °C
50 °C
|
Ambient temperature during storage/transportation
|
|
● min.
● max.
|
-40 °C
70 °C
|
Air pressure acc. to IEC 60068-2-13
|
|
● Operation, min.
● Operation, max.
● Storage/transport, min.
● Storage/transport, max.
|
795 hPa
1 080 hPa
660 hPa
1 080 hPa
|
Relative humidity
|
|
● Operation at 25 ℃ without condensation, max.
|
95 %
|
Connection method
|
|
required front connector
|
Yes
|
Mechanics/material
|
|
Enclosure material (front)
● Plastic
|
Yes
|
Dimensions
|
|
Width
|
45 mm
100 mm
75 mm
|
Height
|
|
Depth
|
|
Weights
|
|
Weight, approx.
|
180 g
|