M-CVM-K2-ITF-402, Power analyzer

M-CVMk2-ITF-402

อัตราค่าจัดส่ง

รายละเอียดสินค้า

DESCRIPTION

Three-phase power analyzer (balanced and unbalanced networks), assembly on panels or DIN rails, with a graphical display, with 4-quadrant measurement.

Other features include:

  • Class 0.2 or 0.5 power and energy
  • Measurement of power quality events (guaranteeing the power supply of the unit by means of a UPS system, battery, etc.)
  • Current measurement .../5 or .../1 A
  • Measurement of the neutral current with a transformer
  • Rating of consumed and generated energy (up to 9 tariffs)
  • RS-485 Modbus/RTU communication
  • Possibility of expansion (up to 3 modules)
  • Backlit VGA graphic screen
  • Instantly shows electrical parameters, maximum and minimum values with date and time
  • Consumed and generated energy meter up to 100 GW·h
  • Universal power supply as standard
  • With ITF technology: galvanic insulation protection

APPLICATIONS

  • Control application for general distribution switchboards and low-, medium- and high-voltage connection points
  • Alarm station, featuring voltage-free digital inputs
  • Submetering station: impulse meter for other services (gas, water, steam etc.) via the digital inputs
  • Measurement transducer: possibility of associating instantaneous parameters with one of the available analogue outputs (0 to 20 mA / 4 to 20 mA)
  • Unit for recording the instantaneous, maximum and minimum parameters, with date and time, via the memory expansion card
  • Power quality analyzer: Harmonic decomposition, up to the 50th order harmonic, asymmetries, flicker, unbalances, overvoltages, gaps, interruptions, etc.
 
 

SPECIFICATIONS

AC POWER SUPPLY
Nominal voltage
85…265 Vc.a. (-15…+10%)
Frequency
50…60Hz
Consumption
<30 VA
Installation category
CAT III 300/520 Vac (IEC 61010)
DC POWER SUPPLY
Nominal voltage
100…300 Vdc
Consumption
<25 W
VOLTAGE MEASUREMENT CIRCUIT
Nominal voltage
300V Ph-N, 520V Ph-Ph
Voltage measuring range
5 ...120% Un
Frequency measuring range
45…65 Hz
Minimum measurement voltage (Vstart)
10 V~
Installation category
CAT III 300/520 V (EN-61010)
Maximum input voltage consumption
<0,6 VA
CURRENT MEASUREMENT CIRCUIT
Nominal current (In)
In/5A, In/1A
Phase current measuring range
1…120% In (In = 5 A)
Primary current measurement
Programmable < 30000 A
Maximum pulse current
100 A
Minimum current measurement
40 mA
Permanent overload
1.2 In
Maximum input current consumption
<0,45 VA (…/5 , …/1)
MEASUREMENT ACCURACY
Phase voltage measurement
± 0,2% ± 2 (20 ... 120% Un)
Power factor measurement
0,5…1
DIGITAL TRANSISTOR OUTPUTS
Type
Optocoupler
Maximum voltage
150 Vdc / 250 V~
Maximum current
100 mA
Maximum resistance RON
25 Ω
DIGITAL INPUTS
Operating voltage
24 Vdc ± 20 %
Minimum signal width
40 ms
Consumption (per input)
<0,5 W
ANALOGUE OUTPUTS
DAC resolution
4000 points
Current mode, nominal range
0-20 mA/4-20 mA
Current mode: maximum load resistance
300 Ω
Response time
< 2 s
COMMUNICATIONS
Protocol
ModBus/RTU, ModBus/TCP
Fieldbus
RS-485 / Ethernet RJ-45
Speed
9600 - 19200 - 38400 - 57600 / Ethernet: 10baseT / 100base /Tx compatible
ENVIRONMENTAL CHARACTERISTICS
Working temperature
-10…+50 ºC
Storage temperature
-20…+65 ºC
Relative humidity (without condensation)
5…95%
Protection class
IP 51 (Front), IP 20 (rear)
MECHANICAL CHARACTERISTICS
Envelope
Self-extinguishing V0 plastic
Weight (kg)
0,44
Size (mm) width x height x depth
144 x 144 x 116 (mm)
STANDARDS
Standards
IEC 664, VDE 0110, UL 94, IEC 801, IEC 348, IEC 571-1, EN 61000-6-3, EN 61000-6-1, EN 61010-1, EN 61000-4-11, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 55011, IEC 62053-22
Certifications
CE, UL, VDE
Electrical safety, Installation category
CAT III 300V / 520V, IEC 61010
Electrical safety, Maximum height (m)
2000
ELECTRICAL SAFETY
Insulation
Double-insulated electric shock protection class II (IEC 61010-1)
 

CONNECTIONS

 

ข้อมูลสินค้า

สินค้าแน่ะนำ